Mitsubishi industrial control products are widely applied across various industrial and mining enterprises. While the quality of these products is assured, the dynamic nature of industrial environments and unclear regulations can lead to system disturbances after installation. Since interference arises from mutual interactions, the impact between components can cause system failures. This makes both theoretical analysis and practical troubleshooting complex, requiring experience in both situational judgment and real-world application.
Based on user feedback, most issues tend to occur during product usage, primarily due to the following reasons:
1. **Long wiring and improper layout**: Large equipment with scattered layouts often result in long, unreasonable wiring paths, leading to poor grounding, formation of interference loops, and generation of line noise that interacts with other equipment.
2. **Improper separation of strong and weak signals**: When power, control, and communication lines are mixed, it increases the risk of interference. Power lines are easier to distinguish, while control signals contain more data and require careful classification based on actual needs.
3. **Interference from related equipment**: Common sources include:
- Inverters and servo devices that generate pulse signals.
- Machines like wire cutters and EDMs that produce pulses and arcs.
- Fluorescent lamps that flicker during startup.
- Relay and contactor release causing reverse peak voltage.
- Nearby devices operating at frequencies close to the system's signal range.
**Control Signal Classification**:
1. **Digital Input**:
- **Dry contacts**: Such as switches, limit switches, and relay contacts. The PLC input current must be maintained between 3.5–4.5 mA for stability. Poor contact or long wires increase susceptibility to interference.
- **Proximity and photoelectric switches**: These are often located far from the PLC and may be affected by large level intervals or pulse widths.
- **Differential encoders**: Suitable for long-distance, high-speed applications, they are less prone to interference compared to open collector types.
2. **Digital Output**:
- **Relays**: Used to drive contactors, solenoid valves, and lights. AC loads can be grouped with power lines, while DC loads depend on voltage and device type.
- **Transistor outputs (DC 5–30V)**: Ideal for low-voltage loads and high-speed signals. Maintain a minimum 30cm distance from power lines to avoid interference.
- **Precautions**: Inductive loads connected to output terminals should use RC snubbers or freewheeling diodes to protect the PLC and external devices.
3. **Analog Input**:
- Typically connected via voltage or current. Long cables, improper connections, or low-quality sensors can introduce noise, especially for small signals. Current-type inputs are recommended for better performance.
4. **Analog Output**:
- Similar to analog input, attention must be paid to signal reliability over long distances, where interference and attenuation can occur.
5. **Communication Lines**:
- **Optical cables**: Immune to electromagnetic interference, ideal for high-performance, low-loss transmission.
- **Coaxial and twisted pair cables**: Provide good performance but are more susceptible to interference. Twisted pairs are cost-effective and suitable for large systems with limited space.
In practice, many users have reported issues with high-speed counting, temperature control, inverters, and servo devices. For example:
- **High-speed counting module AISD62**: Misalignment occurred when the encoder was 30 meters away. Proper separate power supply and wiring improved performance.
- **Thermocouple module FX2N-4AD-TC**: Temperature fluctuations were reduced by connecting the compensation wire to the module’s 0V reference point.
- **Positioning modules**: Interference from motor drivers caused position errors. Filtering and proper shielding helped reduce issues.
- **Inverter FR-E500**: Grounding problems led to display malfunctions. Proper grounding resolved the issue.
- **Inverter FR-A500**: Line noise interference was minimized using a line noise filter between the inverter and motor.
When hardware solutions are not sufficient, software adjustments can also help. For instance, averaging operations can reduce sensitivity to interference, although this is only suitable for non-real-time applications.
These experiences reflect common challenges in industrial control systems, not limited to Mitsubishi products. Due to the complexity and variability of interference, some insights may be incomplete. It is hoped that experienced professionals can contribute additional knowledge to improve system reliability and product credibility.